Level

The SC120 probe transmits a current signal to the CN Indicator Relay, which in turn transforms it into a 4… 20mA signal.   The SC120 can be used for measuring the level within smaller tanks, as the CN Series Indicator Relays have a wide range of sensitivity adjustment. Likewise, it can also be used in larger tanks via the use of steel cable in place of the 316SS rigid rod.

Mandatory Accessories (choose one):

  • CN202 – Indicator Relay
  • CN200 – Indicator Relay
  • CN205 – Indicator Relay

SC120 Capacitive Level Probe

Application: Level Measurement in Liquids & Solids
Consumption: 22mA Max
Adjustment: Sensibility (1, 2, 3 Stages)
Sensitivity: 100 to 5500pF
Accuracy: max error 0.5%
Repeatibility: +/- 1mm
Electrical Connection (Cable entry): Cable Gland 1/2”, 3/4” NPT/ BSP, M12 connector
Process Connection: 3/4” to1 1/2” BSP or NPT, Flanged or Sanitary connection
Wetted Parts: 316 SS, PTFE Coating
Housing Material: Aluminum
Max Pressure: 290 PSI (20 Bar)
Operating Temperature: -10 to 80ºC
Class Protection: IP65 (IEC 60529)