The CF12 Thermal Dispersion Flow Switch with a large aluminum housing (G2) comes standard with a Universal Power Supply: 24Vdc or 85 to 264Vac. This unit offers reliable liquid and gas flow detection ideally suited for just about any Flow/ No Flow application. Unlike the CF12 with either the small nylon housing (N1) or the small aluminum housing (G1), the CF12 with large aluminum housing (G2) comes with two independent SPDT relays (as opposed to just one SPDT relay).
Like all of Sitron’s products, the CF12 can be configured to accommodate our customer’s unique process control requirements. All models can be ordered with a great variety of threaded, flange, or sanitary process connections as well as Halar or epoxy coating for aggressive mediums. The CF12 with large aluminum housing is also offered with extended necks for higher temperature applications up to 120 ºC. And while the CF12 is designed to monitor flow status of liquids and gases, with its no moving parts technology it can also be an ideal solution for liquid level detection.
CF12 - Large Aluminum Housing, G2
Application: | Flow for liquids and gas level for liquids only |
Operating Voltage: | CF12 AC: 85-240Vac (50/60hz) / 125Vdc or CF12 DC: 24Vdc (+/-10%) |
Current Consumption: | +/- 100mA |
Output: | Relay (2x SPDT) 5A - 250Vac |
Set Point Range: | Liquid: 3 cm/s to 3 m/s - Gas: 5 cm/s to 5 m/s |
Accuracy: | +/- 10% |
Repeatabilty: | +/- 1% setpoint |
Response Time: | 1 to 10s |
Gradient Temperature: | 15ºC/min |
Flow Rate Indication: | Red led - Flow is below setpoint / Yellow led - Flow is at setpoint / Green led - Flow is above setpoint |
Enclosure Material: | Aluminum painted |
Electrical Connection: | (2x) Cable gland 1/2' NPT or (2x) ½” NPT entry |
Process Connection: | ½” to 2” BSP or NPT, adjustable, sanitary or flanged connections |
Wetted Material: | 316 Stainless Steel or Halar Coating |
Operating Temperature: | 14 to 176º F (-10 to 80ºC) or extended neck to 248ºF (120ºC) |
Max Pressure: | 100 Bar (others upon request) |
Class Protection: | IP 66 |
Documentation for download
- Pump protection
- High flow alarm
- Low flow alarm
- HVAC monitoring
- Leak detection
- Supply line control
- Fill/Drain control
- Lubricant monitoring
- Cooling water monitoring
- Heat exchanger control
- On/Off valve monitoring
- Oil flow detection
- Air flow monitoring