The TR202 receives a 4…20mA signal and provides (2X) programmable SPDT relay outputs, (1X) Fail Safe relay as well as a passive 4…20mA signal that can be linked in series with a PLC or can be linked with additional TR202 relays. Each relay can work independently or together. In addition, a 3 digit LED indicator provides visual indication between 0…100% of the input signal. The TR202 will work with any type of sensor with a 4…20mA output (i.e. pressures sensors, radar and ultrasonic sensors, temperature sensors, vibration sensors, etc.).
TR 202 Relay
Application: | Converter Current 4...20mA to Relay |
Operating Voltage: | 24Vdc or 100~270Vac |
Input Signal: | 4...20mA (2 wires) analog passive or Active |
Accuracy: | 1% / 0,16mA |
Input Impedance: | 250 ohms |
Protection: | Polarity inversion, Power surges |
Output: | 2x contacts SPDT (5A 250V) |
Adjustment: | Set-point / Output State |
Visualization: | 3 digits 7 segments Display |
Indication (LED): | Green: Output state / Red: Set-Point / Yellow: Fail Safe |
Output State: | Logic inversion via Software |
Fail Condition: | Wire break or short circuit on the input analog signal / Low Signal <2mA / High Signal> 23mA |
Operating Temperature: | -10...60°C |
Enclosure: | ABS (Resistant Thermoplastic) |
Fixation: | DIN rail 35mm or Screws |
Class Protection: | IP40 (IEC 60529) |
Documentation for download
- Any application that requires relay outputs from a 4…20mA sensor